AIR CONDITIONER Cassette type DESIGN & TECHNICAL MANUAL SINGLE INDOOR AU A30LBLU AU A36LBLU OUTDOOR AO A30LBTL AO A30LFTL AO A36LBTL AO A36LFTL...
Page 2
1. INDOOR UNIT CASSETTE TYPE : AU A30LBLU AU A36LBLU D2D_AU034E/04 2010.07.07...
FEATURE MODEL INDOOR UNIT OUTDOOR UNIT AOA30LBTL AUA30LBLU AOA30LFTL AOA36LBTL AUA36LBLU AOA36LFTL FEATURES Energy saving • All DC design • Heat exchange efficiency increased and larger air flow by adoption of new type turbo fan Advancement in comfort ...
Page 5
Wide & powerful airflow The wind is widely delivered by a high efficiency fan and round flap. [ m ] Side view [ m ] Airflow range of 2m / s Improvement of installation & maintenance • Adjustment of nut is possible after installation Mounting position of body can be fine adjusted after Decoration panel mounting.
FUNCTION SETTING Outlet direction selection • Performs operation matched to the number of outlets when 4 directions are unnecessary and outlets are blocked when the ceiling cassette is installed in a corner, etc. 4-way direction 3-way direction 4-way direction mode: Set when there are 4 outlets (shipped state).
REMOTE CONTROLLER WIRED REMOTE CONTROLLER FEATURES Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week) When setting up a timer, operation mode and a temperature ...
FUNCTIONS START/STOP button Pressed to start and stop operation. Set temperature button Selects the setting temperature. Master control button Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY). Fan control button Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH). Economy button Turns the economy efficient mode on and off.
SPECIFICATIONS CASSETTE MODEL Type INVERTER HEATPUMP Indoor unit AUA30LBLU AUA36LBLU Model name Outdoor unit AOA30LBTL AOA30LFTL AOA36LBTL AOA36LFTL Power source 230V~ 50Hz Available voltage range 198-264V~ 50Hz Cooling European energy label Heating 8.50 10.00 Rated BTU/h 29000 34100 Cooling 2.80 - 10.00 2.80 - 11.20 Min.-Max.
DIMENSIONS MODEL : AUA30L, AUA36L Ceiling opening and hanging bolt pitch (Unit : mm) 950 mm(Panel frame) 860 - 910 mm(Ceiling opening) 840 mm(Body frame) 795 mm(Hanging bolt pitch) 50 mm 130 mm 200 mm Refrigerant piping and drain piping positions ...
Page 11
INSTALLATION PLACE (Unit : mm) Strong and durable ceiling 1,500 or more 3,000 or more Ceiling mode “Low” : 2.7 m Ceiling mode “Standard” : 3.2 m Obstruction Ceiling mode “High” : 3.6 m (30 model) 4.2 m (36 model) Floor 3-way directions setting ...
FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Note: Condition 7-1-1. STANDARD MODE Fan speed : High Operation mode : FAN MODEL : AUA30L Ceiling mode : Standard 4-way air outlet Unit : m/s TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER...
Page 16
Note: Condition Fan speed : High Operation mode : FAN MODEL : AUA36L Ceiling mode : Standard 4-way air outlet Unit : m/s TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER...
Page 17
Note: Condition Fan speed : High Operation mode : FAN MODEL : AUA30L Ceiling mode : Standard 3-way air outlet Unit : m/s TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER...
Page 18
Note: Condition Fan speed : High Operation mode : FAN MODEL : AUA36L Ceiling mode : Standard 3-way air outlet Unit : m/s TOP VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER : Upward Unit : m/s SIDE VIEW VERTICAL LOUVER...
Page 19
Note: Condition 7-1-2. SPECIAL UPWARD MODE Fan speed : High Operation mode : FAN MODEL : AUA30L Ceiling mode : Standard 4-way air outlet Unit : m/s SIDE VIEW VERTICAL LOUVER : Special upward MODEL : AUA36L ...
7-2. AIR FLOW 7-2-1. 4-WAY OUTLET MODEL : AUA30L Cooling / Heating Number of Fan speed rotations Airflow (r.p.m) 1600 HIGH 1400 1270 1150 QUIET MODEL : AUA36L Cooling / Heating Number of Fan speed rotations Airflow (r.p.m)
Page 21
7-2-2. 3-WAY OUTLET MODEL : AUA30L Cooling / Heating Airflow Number of Fan speed rotations *Max. *Min. (r.p.m) 1550 1350 HIGH 1350 1200 1250 1100 1100 QUIET MODEL : AUA36L Cooling / Heating Airflow Number of Fan speed rotations...
7-3. FRESH AIR MODEL : AUA30L, AUA36L Air flow volume - Static pressure of Fresh air intake characteristic Duct (Inside Dia. ø70mm) Duct Fan Static pressure required to take in fresh air Air flow (m /min) Installation ...
7-4. DUCT CONNECTION MODEL : AUA30L, AUA36L Outlet air AUA30L Duct (Inside Dia. 350mm×100mm) Fan speed High Fan speed Qutiet L=10m L=5m L=1m Air flow (m /min) AUA36L Fan speed High Fan speed Quiet L=10m L=5m L=1m Air flow (m /min) - (01 - 20) -...
Page 24
PRECAUTIONS WHILE CONNECTING AIR OUTLET DUCT zConnect the air outlet duct at up to two locations among the four duct connection locations. (Do not connect ducts at three or more locations.) zBlow-off pattern when a branch duct is installed ...
ELECTRIC CHARACTERISTICS Model Name AU A30L AU A36L Voltage 230V ~ Power Supply Frequency 50Hz Max Operating Current (Indoor unit) Circuit breaker Wiring Spec. Connection Cable 1.5-2.5 (Indoor unit to outdoor unit) Limited wiring length - (01 - 24) -...
SAFETY DEVICES Model Protection form AU A30L AU A36L Circuit protection Current fuse (PCB) 3.15A 250V Thermal protection 110±15°C OFF Fan motor protection program 105±15°C ON - (01 - 25) -...
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS Control input CN102 — (Operation/Stop) See external CN103 — Operation status output input/output settings for details. — Fresh air control output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop) The air conditioner can be remotely operated by means of the following on-site work. Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a connector on the external control PC board and turning it ON.
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m.
Page 31
FRESH AIR CONTROL OUTPUT A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example Indoor Connected unit control PC board Ex.) Fan Ex.) Relay unit 12 V Connector...
FUNCTION SETTING 12-1. INDOOR UNIT INDOOR UNIT DIP SW Setting forbidden Remote control unit signal code Jumper Wire Setting forbidden SWITCH POSITION MAIN PCB Indoor unit Printed circuit board JUMPER WIRE SETTING Remote control unit signal code Indoor unit setting (...
12-2. WIRED REMOTE CONTROLLER Can not be used. (Do not change) Dual remote controller setting Can not be used. (Do not change) DIP SW Can not be used. (Do not change) Can not be used. (Do not change) Memory backup setting SWITCH POSITION ...
(4) Press the set temperature buttons ( ) to select the setting CAUTION value. • Confirm whether the wiring work for outdoor unit has been The display flashes as shown to the right during setting value finished. selection. • Confirm whether the ccover for electric control box on the outdoor unit is close.
Page 35
Setting the Outlet Directions Setting record • Select the setting values in the table below for using a 3-way • Record any changes to the settings in the following table. outlet. (The unit is factory-set to “00”.) Setting Setting Value Setting Description Function Number Setting Value...
OPTIONAL PARTS Exterior Parts name Model No. Summary Air outlet shutter plate is Air outlet UTR-YDZC installed at the air outlet when shutter plate 3-way direction is performed. Wide panel hides the gap Wide panel UTG-AGYA-W between the ceiling hole and the Decoration panel.
Page 37
Exterior Parts name Model No. Summary It can be taken in fresh air of up to 10% of “high” air volume Fresh air intake UTZ-VXGA of the indoor unit by attaching Fresh Air Intake Kit to cassette type indoor unit. - (01 - 34) -...
SPECIFICATIONS Type INVERTER HEATPUMP Model name AO A30LBTL AO A36LBTL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current 15.0 15.0 Cooling 3600 4000 Airflow rate Heating 3800 3800 Type × Q'ty Propeller × 1 Motor output Cooling Sound pressure level...
Page 41
Type INVERTER HEATPUMP Model name AO A30LFTL AO A36LFTL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current 15.0 15.0 Cooling 3600 3800 Airflow rate Heating 3600 3800 Type × Q'ty Propeller × 1 Motor output Cooling Sound pressure level...
DIMENSIONS MODEL : AOA30LB, AOA36LB, AOA30LF, AOA36LF (Unit : mm) Top view Front view Side view Air flow Bottom view INSTALLATION PLACE When there are obstacles at the back, When there are obstacles at the back, When there are obstacles at the back side(s), and top.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DEFFERENCE This table is created using the maximum capacity. MODEL : AOA30LB, AOA30LF Pipe length (m) COOLING 0.908 0.894 0.876 0.935 0.923 0.909 0.891 1 Indoor unit is upper 0.968 0.951 0.938...
Page 49
This table is created using the maximum capacity. MODEL : AOA36LB, AOA36LF Pipe length (m) COOLING 0.908 0.894 0.876 0.935 0.923 0.909 0.891 1 Indoor unit is upper 0.968 0.951 0.938 0.924 0.906 than outdoor unit 0.982 0.972 0.954 0.942...
AIR FLOW MODEL : AOA30LB COOLING Number of rotations Air flow (r.p.m) 3600 1000 2119 HEATING Number of rotations Air flow (r.p.m) 3800 1056 2236 MODEL : AOA36LB COOLING Number of rotations Air flow (r.p.m) 4000 1111...
Page 52
MODEL : AOA30LF COOLING Number of rotations Air flow (r.p.m) 3600 1000 2119 HEATING Number of rotations Air flow (r.p.m) 3600 1000 2119 MODEL : AOA36LF COOLING Number of rotations Air flow (r.p.m) 3800 1056 2236...
ELECTRIC CHARACTERISTICS AO A30LB AO A36LB Model name AO A30LF AO A36LF Voltage 230 ~ Power supply Frequency *1) Max. operating current 17.0 20.0 Starting current 15.0 Main fuse (Circuit breaker) current *2) Wiring spec. Power cable 5.3 - 6.0 *3)Limited wiring length *1) The maximum current is the total current of indoor unit and outdoor unit.
SAFETY DEVICES Model Protection form AO A30LB AO A36LB AO A30LF AO A36LF Current fuse (NEAR THE TERMINAL) 25A 250V Circuit protection Current fuse (FILTER PRINTED CIRCUIT BOARD) 10A 250V Current fuse (MAIN PRINTED CIRCUIT BOARD) 3.15A 250V OFF : 140±20°C Fan motor protection...