[ II Restrictions ]
CAUTION
1) Wiring should be covered by insulation tube with supplementary insulation.
2) Use relays or switches with IEC or equivalent standard.
3) The electric strength between accessible parts and control circuit should have 2750V or more.

Example of wiring connection

CN51
Distant control
Relay circuit
board
L
1
L
2
Preparations
in the field
L1 : Outdoor unit error display lamp
L2 : Compressor operation lamp (compressor running state)
X, Y : Relay (coil =<0.9W : DC12V)
1. Optional part : PAC-SC37SA-E or field supply.
CN3N
2
Relay circuit
Adapter 2
X
Y
Preparations
Maximum cable
in the field
length is 10m
CN3D
Adapter 2
Relay circuit
X
Y
Preparations
in the field
Maximum cable
length is 10m
X : Low-noise mode
Y : Compressor ON/OFF
X,Y : Relay Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
HWE07130
Adapter 1
Outdoor unit
control board
X
Y
CN51
Y
X
5
4
3
Maximum cable
length is 10m
Outdoor unit
control board
CN3N
1
OFF
2
Y
ON
3
X : Cooling / Heating
Y : Validity / Invalidity of X
X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Outdoor unit
control board
CN3D
1
2
3
CN3S
Relay circuit
Adapter 2
X
Preparations
in the field
Maximum cable
length is 10m
X : Relay
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
Snow sensor : The outdoor fan runs when X is closed
in stop mode or thermostat mode.
2. Optional part : PAC-SC36NA-E or field supply.
X
OFF
ON
Normal
Cooling
Heating
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
Relay circuit
X
Preparations
in the field
Maximum cable
length is 10m
X : Low-noise mode
X : Relay
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
Low-noise mode : The noise level is reduced by controlling the maximum
fan frequency and maximum compressor frequency.
- 23 -
Outdoor unit
control board
CN3S
1
2
3
Outdoor unit
Adapter 2
control board
CN3D
1
2
3
GB