Mitsubishi Electric PURY-(E)P200 Service Handbook page 267

Hide thumbs Also See for PURY-(E)P200:
Table of Contents
[ IX Troubleshooting ]
Valve closed
A
E
B
80 - 100 pulses
HWE07130
D
C
Valve open
Fully open: 1400 pulses
Pulses
*When the power is turned on, the valve closing signal of 2200 pulses
will be output from the indoor board to LEV to fix the valve position.
It must be fixed at point A.
When the valve operates smoothly, no sound from LEV or no vibration
occurs, however, when the pulses change from E to A in the chart or
the valve is locked, a big sound occurs.
*Whether a sound is generated or not can be determined by
holding a screwdriver against it, then placing your ear against the handle.