High-Pressure Sensor Fault (63Hs1) (Outdoor Unit) - Mitsubishi Electric PURY-(E)P200 Service Handbook

Hide thumbs Also See for PURY-(E)P200:
Table of Contents
[ IX Troubleshooting ]
1. Error Code
5201

High-pressure sensor fault (63HS1) (Outdoor unit)

2. Error definition and error detection method
If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to anti-
restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more.
If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and
the error code "5201" will appear.
During 3-minute antirestart mode, preliminary errors will be displayed on the LED display.
A error is not detected for 3 minutes after the compressor start, during defrost operation, or 3 minutes after defrost operation.
3. Cause, check method and remedy
(1)
High pressure sensor failure
(2)
Pressure drop due to refrigerant leak
(3)
Torn wire coating
(4)
A pin on the male connector is missing or contact failure
(5)
Disconnected wire
(6)
High pressure sensor input circuit failure on the control board
HWE07130
Cause
- 205 -
Check method and remedy
Refer to the page on the troubleshooting of
the high pressure sensor.
(9 [4] -1-(page 251))