Control At Initial Start-Up; Flowchart Of Initial Operation - Mitsubishi Electric PURY-(E)P200 Service Handbook

Hide thumbs Also See for PURY-(E)P200:
Table of Contents
[ VII Control ]

-10- Control at Initial Start-up

When started up for the first time before 12 hours have elapsed after power on, the unit goes into the initial startup mode.
At the completion of the initial operation mode on the OC and OS, they will go into the normal control mode.

1. Flowchart of initial operation

(1) P200, P250, P300, P350, P400, EP200, EP300 models
(2) P450, P500, P550, P600, P650, P700, P750, P800, EP400, EP450, EP500, EP550, EP600 models
The compressor on the OC starts up.
F
The total operating load of the indoor unit
after 5 minutes of operation is P250 or above.
The compressor on the OC remains in operation, and the
compressor on the OS starts up.
50
F
Completed in the integrated operation time of 35 minutes.
or
F < 50Hz (both OC and OS)
Completed in the integrated operation time of 90 minutes.
HWE07130
Initial startup mode starts.
50
F
Completed in the integrated operation time of 35 minutes.
or
F < 50Hz
Completed in the integrated operation time of 90 minutes.
Initial startup mode complete
Initial startup mode starts.
60Hz
*1 Qj:Total capacity (models) code
(*1 Qj
50)
Yes
60Hz (both OC and OS)
Initial startup mode complete
60Hz
Refer to the " Control - 2. Function of the switch (Indoor unit) - (1) Dipswitches- 2) SW2"
(page 84) for the capacity code.
No
The compressor on the OC starts up.
*2
50
Completed in the integrated operation time of 35 minutes.
or
Completed in the integrated operation time of 90 minutes.
*3
Both the OC and OS stop.
The startup sequence of the OC and OS is rotated.
The compressor on the OS starts up.
50
Completed in the integrated operation time of 35 minutes.
or
Completed in the integrated operation time of 90 minutes.
*2
The air conditioning load is too small
for both the OC and the OS to
simultaneously stay in operation.
*3
The air conditioning load is
high enough for both OC and OS to
simultaneously stay in operation.
- 129 -
F
60Hz (OC)
F < 50Hz (OC)
F
60Hz (OS)
F < 50Hz (OS)
GB