M-Net Address Settings; Address Settings List - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents

[2-4 M-NET Address Settings ]

2-4

M-NET Address Settings

2-4-1

Address Settings List

1. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controller
CITY MULTI
Main/sub unit
indoor unit
M-NET
adapter
M-NET con-
trol interface
Free Plan
adapter
LOSSNAY, OA processing unit
ATW
Booster Unit
Water Hex Unit
ME remote
Main remote
controller
controller
Sub remote
controller
MA remote controller
CITY MULTI outdoor unit
Auxiliary out-
BC controller
door unit
(main)
BC controller
(sub1, 2)
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting
range.
*2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50."
*3. To set the ME remote controller address to "200," set the rotary switches to "00."
*4. Some models of indoor units have two or three control boards.
Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board
address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, and OS. They are designated as OC, and OS in
the descending order of capacity (ascending order of address if the capacities are the same).
*6. No address settings are required for units in a system with a single outdoor unit (with some exceptions).
Address setting is required if a sub BC controller is connected.
*7. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the setting
range.
HWE1314A
Sym-
Address
bol
setting
range
IC
0, 01 to
Assign the smallest address to the main indoor unit in the
*1 *4 *6*7
50
group, and assign sequential address numbers to the rest of
the indoor units in the same group.
In an R2 system with a sub BC controller, make the settings
for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC controller
(ii) Indoor unit to be connected to sub BC controller 1
(iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that the for-
mula "(i) < (ii) < (iii)" is true.
LC
0, 01 to
Assign an arbitrary but unique address to each of these units
*1 *4 *6 *7
50
after assigning an address to all indoor units.
BU
AU
RC
101 to 150
Add 100 to the smallest address of all the indoor units in the
same group.
RC
151 to
Add 150 to the smallest address of all the indoor units in the
*3
200
same group.
MA
No address settings required. (The main/sub setting must be made if 2 re-
mote controllers are connected to the system.)
OC
0, 51 to
Assign an address that equals the lowest address of the in-
*1 *2 *6
OS
100
door units in the same refrigerant circuit plus 50.
*7
Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same re-
frigerant circuit are automatically designated as OC and
*5
OS.
BC
0, 51 to
Assign an address that equals the address of the outdoor
*1 *2 *6
100
unit in the same refrigerant system plus 1.
If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub BC controller,
use a different, unused address within the setting range.
BS1
51 to 100
Assign an address to both the sub BC controller 1 and 2
*2
BS2
that equals the lowest address of the indoor units that
are connected to each of them plus 50.
If a sub BC controller is connected, the automatic startup
function is not available.
- 25 -