Simple Check On Inverter Circuit Components; Troubleshooting Problems With Igbt Module - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents
[8-10 Troubleshooting Inverter Problems ]
8-10-14

Simple Check on Inverter Circuit Components

Turn off the power of the unit and wait at least 10 minutes, check that the voltage between the FT-P and FT-N terminals on
the INV board or between the SC-P and SC-N terminals is 20 VDC or less, and then remove the applicable parts from the
control box.
Part name
IGBT module
Refer to the following page(s). [8-10-15 Troubleshooting Problems with IGBT Module](page 345)
Rush current pro-
Measure the resistance between terminals R1 and R5: 22 Ω±10%
tection resistor
R1, R5
Electromagnetic
relay
72C
EP200-EP450
EP500
DC reactor DCL
Measure the resistance between terminals: 1Ω or lower (almost 0 Ω)
Measure the resistance between terminals and the chassis: ∞
8-10-15

Troubleshooting Problems with IGBT Module

Measure the resistances between each pair of terminals on the IGBT with a tester, and use the results for troubleshooting.
The terminals on the INV board are used for the measurement.
1) Notes on measurement
Check the polarity before measuring. (On the tester, black normally indicates plus.)
Check that the resistance is not open (∞ Ω) or not shorted (to 0 Ω).
The values are for reference, and the margin of errors is allowed.
The result that is more than double or half of the result that is measured at the same measurement point is not allowed.
Disconnect all the wiring connected the INV board, and make the measurement.
2) Tester restriction
Use the tester whose internal electrical power source is 1.5V or greater
Use the dry-battery-powered tester.
(The accurate diode-specific resistance cannot be measured with the button-battery-powered card tester, as the applied volt-
age is low.)
Use a low-range tester if possible. A more accurate resistance can be measured.
HWE1314A
This electromagnetic relay is rated at DC12V and is driven by a coil.
Check the resistance between terminals
Upper
1
2
3
Installation
direction
6
4
3
1
2
Judgment method
4
Check point
Coil
Between Terminals 5 and 6
Between Terminals 1 and 2
Contact
Between Terminals 3 and 4
5
Check point
Coil
Between 1-2 pins and inverter
RY3-RY4
boards RY3 and RY4
Inverter board FT-R21 and SC-P
Contact
*Faston terminal and SC-P
RY3-RY4
wiring removed
- 345 -
Checking criteria( )
W
Not to be short-circuited
(Center value 75 ohm)
Checking criteria
160Ω±10%
Inverter board CNRY
Open: ∞
Inverter board CNRY
When 12 VDC is being input: 0Ω
GB