Troubleshooting Problems With Major Components On Bc Controller; Pressure Sensor - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents

[8-9 Troubleshooting Problems with Major Components on BC Controller ]

8-9
Troubleshooting Problems with Major Components on BC
Controller
8-9-1

Pressure Sensor

Troubleshooting flow chart for pressure sensor
Check whether the pressure sensor or the
connectors of P1 and P3 are connected,
properly
NO
Operating at the moment?
On the self-diagnosis monitor, measure
Outdoor high-pressure 63HS1
Outdoor low-pressure 63LS
BC controller pressure P1 (liquid side)
and P3 (intermediate part)
Check whether the result is
63HS1
P1
All the compressors of the outdoor units to
which the BC controller is connected are stopped.
Check P1 and P3 on the self-diagnosis
LED, and check that the detected
pressure is 0.098MPa [14psi] or less.
Check that the difference between each
detected pressure is 0.098MPa [14psi] or less.
Both the board and the pressure sensor are normal.
Check whether the refrigerant pipe and the
transmission line are connected correctly
between the indoor unit and the BC controller.
HWE1314A
START
Note 1
OK?
YES
Note 2
P3
63LS
Check whether the refrigerant pipe
NO
and the transmission line are
OK?
connected correctly between the indoor
unit and the BC controller.
YES
10 minutes or longer after
the operation stops?
NO
NO
OK?
NO
Is Pd
OK?
YES
Fix the relation between the
NO
refrigerant piping and the
OK?
transmission line.
YES
Repair the fault.
Fix the relation between
NO
OK?
the refrigerant piping
and the transmission line.
YES
Check whether the contact of the pressure
sensor connector in trouble is not faulty.
NO
Remove the pressure sensor connector
P1
P3 Ps?
from the board, and check the pressure.
YES
Short-circuit between connecter pins #2 and #3
on the circuit board, and check the pressure.
Replace the pressure sensor, which detects
less than 6MPa [870psi] pressure, with the
pressure sensor, which detects 6MPa [870psi]
or more pressure, check the pressure, and
check whether the detected pressure is
displayed normally.
Replace the pressure sensor.
- 326 -
Note 3
NO
OK?
YES
Note 4
Restore contact failure.
NO
Pressure 0MPa [0psi]
YES
NO
6MPa [870psi] pressure
or more is displayed.
YES
NO
OK?
YES
Replace the board.