1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
Outdoor units
P200
YLM-A(1)
P250
YLM-A(1)
P300
YLM-A(1)
P350
YLM-A(1)
P400
YLM-A(1)
P400
YSLM-A(1) P200YLM-A(1) P200YLM-A(1)
P450
YLM-A(1)
P450
YSLM-A(1) P250YLM-A(1) P200YLM-A(1)
P500
YLM-A(1)
P500
YSLM-A(1) P250YLM-A(1) P250YLM-A(1)
P550
YSLM-A(1) P300YLM-A(1) P250YLM-A(1)
P600
YSLM-A(1) P300YLM-A(1) P300YLM-A(1)
P650
YSLM-A(1) P350YLM-A(1) P300YLM-A(1)
P700
YSLM-A(1) P350YLM-A(1) P350YLM-A(1)
P750
YSLM-A(1) P400YLM-A(1) P350YLM-A(1)
P800
YSLM-A(1) P400YLM-A(1) P400YLM-A(1)
P850
YSLM-A(1) P450YLM-A(1) P400YLM-A(1)
P900
YSLM-A(1) P450YLM-A(1) P450YLM-A(1)
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE1314A
Composing units
Maximum total ca-
pacity of connect-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
- 21 -
Maximum number
of connectable in-
able indoor units
door units
100 - 300
125 - 375
150 - 450
175 - 525
200 - 600
200 - 600
225 - 675
225 - 675
250 - 750
250 - 750
275 - 825
300 - 900
325 - 975
350 - 1050
375 - 1125
400 - 1200
425 - 1275
450 - 1350
Types of connect-
able indoor units
20
P15 - P250 models
R410A series in-
25
door units
30
35
40
45
50
GB