[5-1 Dipswitch Functions and Factory Settings ]
(3) Fan board (Control box side, Fan box side)
Switch
SW1
1
Enabling/Disabling no-load opera-
tion
No-load operation will continue for
approximately 30 seconds, and
then the unit will come to an ab-
normal stop. For details, refer to
the following page(s). [8-10-9
Checking the Fan Inverter for
Damage at No Load](page 342)
2
3
4
5
Address setting (Control box side)
6
Address setting (Fan box side)
Only the addresses are preset before shipment (All other switches are set to OFF.) Unless otherwise specified, leave the
switch to OFF where indicated by "-," which may be set to OFF for a reason.
Set SW1-5 on the control-box-side fan board to ON (address = 5). Set SW1-6 on the fan-box-side fan board to ON (address
= 6).
Leave SW1-1 to OFF during normal operation. Setting this switch to ON will disable the error detection function and may result
in equipment damage.
HWE1314A
Function according to switch
Function
No-load oper-
ation disabled
-
-
-
- 130 -
setting
OFF
ON
No-load oper-
ation enabled
-
-
-
-
-
-
0
5
0
6
Switch setting timing
Anytime after power on
-
-
-
Before power on
Before power on
GB