Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook page 140

Table of Contents
[5-1 Dipswitch Functions and Factory Settings ]
(2) INV board
1) PURY-P200, P250, P300, P350, P400, P450, P500YLM-A(1)
PURY-EP200, EP250, EP300, EP350, EP400, EP450YLM-A
Connector
CN6 short-
Enabling/disabling the following error
circuit con-
detection functions;
nector
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
(5301 Detail No.117)
IPM open/ACCT erroneous wiring
(5301 Detail No. 119)
Detection of ACCT erroneous wiring
(5301 Detail No.120)
CN6 short-circuit connector is mated with the mating connector.
Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
2) PURY-EP500YLM-A
Switch
SW001
Detects or ignores the following errors
ACCT/DCCT sensor fault (5301 Detail
No. 115 and 116)
ACCT/DCCT sensor circuit fault (5301
1
Detail No. 117 and 118)
Open-circuited IPM/Loose CNCT2
connector (5301 Detail No. 119)
Detection of faulty wiring (5301 Detail
No. 120)
2
The default settings for all switches are OFF. Unless otherwise specified, leave the switch that are indicated by "-" to OFF,
which may be set to OFF for a reason.
Leave SW001 to OFF during normal operation. Setting this switch to ON disables the error detection function and may result
in equipment damage.
HWE1314A
Function according to connec-
Function
Error detec-
tion enabled
Function according to switch
Function
Error detec-
tion enabled
-
- 129 -
tor
Enabled
Disabled
Error detec-
tion disable
(No load op-
eration is pos-
sible.)
setting
Enabled
Disabled
Error detec-
tion disable
(No load op-
eration is pos-
sible.)
-
-
Setting timing
Enabled
Disabled
Anytime after power on
Switch setting timing
Anytime after power on
-
GB