PN 292-118
X47 Universal Relay Pack
Installation Guide
Note: This picture is
for reference only.
The production
enclosure is
available only in
Warm Grey.
The X47 Universal Relay Pack (PN 201-147) is an INNCOM
Integrated Room Automation System (IRAS) device designed
for guestroom controls. The X47 provides five relay outputs
used to switch a variety of loads, including fan coil units
(FCU) and light-duty general loads. The X47 can integrate
with and receive data from multiple points throughout the
IRAS using low-voltage wired communication (S5bus),
infrared (IR) communication (when connected to IR Eye 5), or
radio frequency (RF) communication (when connected to a
PC502). The X47 comes in 24VAC (low-power) or 100-
277VAC (line-power) versions.
Installation
CAUTION!
!
•
The X47 is intended for indoor use only.
•
The X47 installer must be a trained, experienced
service technician.
•
All wiring must comply with local codes and
ordinances.
•
The X47 is intended for indoor use only.
•
Failure to follow the instructions provided with the
product could damage the product or cause a
hazardous condition.
Wiring
Figure 1 shows the X47 line-voltage and 24VAC connectors;
Figure 2 shows the communication headers; and Figure 3
shows a typical connection to an FCU.
Figure 2 X47 Headers
Figure 1 Connectors
Line-Voltage Connections: The phase (hot) and neutral
connections are defined on the product label.
Low-Voltage Power/Communications Connection: The
X47 can provide 12VDC 240mA output class-2 power and
S5bus for IRAS devices.
Figure 1 Communications Headers
Typical Fan Coil Unit Connections
FCU
HEAT
COOL
LOW FAN
MED FAN
M
HIGH FAN
NEUT/L2
*
LINE/L1
*Note: Typically Valve and Fan Power use L1/Line Power
Figure 3 Typical FCU Connections
Copyright 2013 INNCOM by Honeywell
Earth
X07
LOGIC BOARD